[ Specification ]
- Type : Ultraviolet and Infrared, Indoor, Explosion-proof, Particulate
- Nominal sensing range : 40 m
- Sensing angle : 90°, Cone type
- Operating temp. : -40 ~ +75°C
- Humidity : 0~95 %
- Explosion proof :
- – Ex d IIC T5/T6 IP67 (KGS)
- – Ex tD A21 IP67 T100°C (KGS)
- water tight : IP67 (KGS)
- Output signal
- – Relay
- Fire : 1A ( 250 VAC, 30 VDC ), A connect point
- Error : 1A ( 250 VAC, 30 VDC ), A-B connect point
- – 4~20 mA
- – RS485
- Function
- – Diagnostic sensor fault enable – Self test
- – Remote self diagnostic ON / OFF control ( BIT )
|
[ Structure ]
- Material : Aluminum 6061
- Surface : Anodizing Process
- Color : Blue
- Weight : About 0.53 kg
- External : 64 MM × 64 MM × 75 mm, Hexahedral, Connector 1/2 inch PF
[ Electrical ]
- Power Consumption : 2.0 W minimum / 3.6 W maximum
- Voltage : DC 24 V, ( 17~32 V, pulsating current available)
- Current
- – Idle(Sensing) : 55 mA
- – Fire (Activating, Emergency) (Sensing) : 90 mA
- – Self test : 120 mA cable recommended.
- Electromagnetic Compatibility : EMC Protected
|