loader image
Get Brochure
Flame DetectorUVIR Flame Detector

UVIR Flame Detector | RFD-2000X

Flame Detector RFD-2000X is a UV / IR type Flame Detector with international certifications.

  • Identify fire when both UV and IR sensors simultaneously detect the presence of a flame.
  • Maximum 30 meters of detection range with a 90 degree cone of vision.
  • Permits operation at Hazardous areas.
  • User selectable output options among Relays, 4-20 ㎃ stepped output, and RS-485.
Highlights
  • UV / IR Dual sensors
  • Enhanced False Alarm Immunity against sunlight and artificial false alarm sources
  • Approval for Explosion Proof and Dust Ignition proof.
  • High reliability in operation with Automatic and Manual Self Diagnosis
  • Flame Detector RFD-2000X is suitable for hazardous areas such as Oil, Gas stations and Petrochemical plants
  • Field selectable sensitivity and delay time

Specification

[  Specification  ]

  • Type : Ultraviolet and Infrared
  • Detection Range : 100 ft (30 m) for N-Heptane fire
  • Field of View : Horizontal 90°, Vertical 90°
  • Temperature Range Operating : -40℃ to +75℃
  • Storage : -50℃ to +80℃
  • Humidity Range : 0 to 95 % relative humidity
  • performance : FM3260, EN 54-10 (CPR, LPCB)
  • Explosion proof :
  • – Ex d IIB+H2 T6 IP67 (KGS)
  • – Class I Division 1 Groups B,C and D (FMUS)
  • – Class II/III Division 1 Groups E,F and G (FMUS)
  • – T6: -40°F (-40°C) to + 176°F (+75°C) (FMUS)
  • – IP67/NEMA 4X(FMUS)
  • – II 2 G Ex db IIB+H2 T6(ATEX)
  • – Ex db IIB+H2 T6(IECEx)
  • water tight : IP67(KGS)
  • Output
  • – Relay
  • · Fire Alarm, Fault Alarm, Warning Alarm
  • · From A or B Selectable, 28VDC, 2A
  • – 4-20mA
  • – RS-485
 [  Structure  ]

  • Dimensions : W134 x H117 x D120 (mm)
  • W5.3 x H4.6 x D4.7 (inch)
  • Enclosure Material : Stainless steel 316
  • Shipping Weight : 3.4 kg
  • Color : Metal
  • Conduit Entry Size : 2 x 1/2 inch NPT, M20X1.5

[  Electrical  ]

  • Operating Voltage : Typical DC 24 V (17 to 32)
  • Power Consumption : 2.0 W minimum / 3.6 W maximum at 32 VDC
  • Wiring : 14 AWG (2.08mm2) to
  • 24 AWG (0.205mm2) shield cable recommended.
  • Electromagnetic Compatibility : EMC Protected
Certificates and Documents