[ Specification ]
- Type : Triple Infrared
- Detection Range : 200 ft (60 m (FM), 50 m (KFI)) for n-Heptane fire
- Field of View : Horizontal 90°, Vertical 90°
- Temperature Range Operating : -40℃ to +75℃
- Humidity Range : 0 to 95 % relative humidity
- performance :
- – FM3260
- – GB 15631-2008 (CCC)
- Explosion proof :
- – Ex d IIB+H2 T5 IP66/67 (KGS)
- – Class I Division 1 Groups B,C and D(FM)
- – Class II/III Division 1 Groups E,F and G(FM)
- – II 2G Ex db IIB+H2 T5 Ta= -40°C to 75°C IP66/67(ATEX)
- – Ex db IIB+H2 T5 Ta=-40°C to 75°C IP66/67(IECEx)
- – Ex dIIB+H2 T5 Gb(NEPSI)
- Output
- – Relay
- · Fire Alarm, Fault Alarm, Warning Alarm
- · From A or B Selectable, 30 VDC, 3 A
- – 4-20 mA
- – RS-485
|
[ Structure ]
- Dimensions : W134 x H117 x D109 mm
- W5.3 x H4.6 x D4.3 Inch
- Enclosure Material : Stainless steel 316
- Shipping Weight : 4.5 kg
- Color : Metal
- Conduit Entry Size : 2 x 1/2 inch NPT, M20X1.5
[ Electrical ]
- Operating Voltage : Typical DC24V (17 to 32)
- Power Consumption : 3.6W minimum /4.8W maximum at 30 VDC
- Wiring : 14AWG (2.08mm2) to
- 24AWG (0.205mm2) shielded cable recommended.
- Electromagnetic Compatibility : EMC Protected
|