loader image
Get Brochure
Flame DetectorFlammable Gas Detector

Flammable Gas Detector DB100

Flammable Gas Detector DB100 is a “SMART” gas detector designed to detect and monitor toxic (CO, H2S, HCI, etc.), oxygen, and VOC gases in the air by applying electrochemical, galvanic, and PID sensors.

  • Flammable Gas Detector DB100 is an intelligent electronic device that applies Rezontech’s unique algorithm. It has a user interface and a comprehensive fault diagnosis function. In addition, the transmitter design is characterized by applying Rezontech’s advanced technology suitable for electrochemical, galvanic, and PID sensors.
  • When assembling the sensor that detects gas, stainless steel was applied. The transmitter housing is coated with epoxy on aluminum to prevent corrosion and designed with a pressure resistant explosion proof structure.
Highlights
  • Explosion proof construction for internal pressure can be installed in high-risk gas leakage areas
  • Continuous detection of oxygen and toxic gases by applying excellent sensors
  • Self diagnosis function and various algorithms secure stability and reliability
  • Measured concentrations and operation status are indicated on the LCD or OLED display
  • 2 gas alarms, 1 fault displayed and relay contact output
  • Remote calibration and program settings are available using the Magnet bar
  • Multiple output options, analog 4-20 mA and digital communication signal RS-485, Modbus Compatible
  • Convenient structure for calibration and maintenance

Specification

 [ Basic Information ] 

Measuring gas Toxic O2 VOC
Measuring method Electrochemical Electrochemical

or Galvanic

PID
Measurement range 0 ~ αppm 0~25 % vol 0 ~ 10 ppm,
0 ~ 5000 ppm
Response Rate T90 < 30~90 secs T90 < 10 secs
Measuring method Diffusion type
 Operating temperature T6 = -40 to 60℃, T4= -40 to 80℃
Storage temperature 0℃ ~ +20℃
Operating humidity 0 ~ 90 %
  • Explosion proof class : Ex d IIC T6, T4 (KCs)
  •                    Ex db IIC T6/T4 Gb (KCs)
  •                    Ex tb IIIC T85℃/T135℃ Db (IECEx)
  •                    Also Ex db IIC T6/T4 Gb (ATEX)
  • Water and dust tight : IP66
  • Output signal
  • – Analog Output Signal : 4-20 mA DC(sink or source),
  •           Conductor-loop resistance : 600 ohm max. @ 24 VDC
  • – Digital Output Signal (Option)  : RS-485 MODBUS RTU
  • – Relay (Option)  : Alarm1, Alarm2, Fault (3A @ 30 VDC , SPDT)
[  Mechanical  ]

  • Material : Housing  / ALDC (Epoxy coating),Sensor: SUS316
  • Weight : Approx.1.80 ㎏
  • Dimension : 150 mm (W) × 173 mm (H) × 112 mm (D)

[ Electrical ]

Gas type Toxic, O2 VOC
Operating voltage 24 VDC (18 to 31 VDC)
Power consumption         1.4 W@24V DC 3.6W@24 VDC
Max. : 2.0 W@24 VDC 4.0W@24 VDC
Cables 3 wire shield cable (CVVS or CVVSB1.5sq)
Transmission distanc Max. : 3,000 m 1,500 m
Certificates and Documents