loader image
Get Brochure
Flame DetectorIR3 Flame Detector

IR3 Flame Detector | RFD-3000X

Flame Detector RFD-3000X is a Triple IR (IR3) Flame Detector with international certifications.

  • Identify fire by analyzing the IR wavelengths of a long distance flame.
  • Maximum 60 meters of detection range with a 90 degree cone of vision.
  • Permits operation at Hazardous areas.
  • User selectable output options among Relays, 4-20 ㎃ stepped output, and RS-485.
Highlights
  • Multispectrum IR sensors
  • Approval for FM, ATEX, IECEx, CCC, NEPSI, KFI and KGS
  • High reliability in operation with Automatic and Manual Self-Diagnosis
  • Enhanced False Alarm Immunity against sunlight and artificial false alarm sources
  • Approval for Explosion-Proof and Dust Ignition proof
  • Flame Detector RFD-3000X is suitable for hazardous areas such as Oil, Gas stations and Petrochemical plants
  • Excellent resistance to corrosion
  • Field selectable sensitivity and delay time.

Specification

[  Specification  ]

  • Type : Triple Infrared
  • Detection Range : 200 ft (60 m (FM), 50 m (KFI)) for n-Heptane fire
  • Field of View : Horizontal 90°, Vertical 90°
  • Temperature Range Operating : -40℃ to +75℃
  • Humidity Range : 0 to 95 % relative humidity
  • performance :
  •   – FM3260
  •   – GB 15631-2008 (CCC)
  • Explosion proof :
  •   – Ex d IIB+H2 T5 IP66/67 (KGS)
  •   – Class I Division 1 Groups B,C and D(FM)
  •   – Class II/III Division 1 Groups E,F and G(FM)
  •   – II 2G Ex db IIB+H2 T5 Ta= -40°C to 75°C IP66/67(ATEX)
  •   – Ex db IIB+H2 T5 Ta=-40°C to 75°C IP66/67(IECEx)
  •   – Ex dIIB+H2 T5 Gb(NEPSI)
  • Output
  •   – Relay
  •     · Fire Alarm, Fault Alarm, Warning Alarm
  •     · From A or B Selectable, 30 VDC, 3 A
  •   – 4-20 mA
  •   – RS-485
 [  Structure  ]

  • Dimensions : W134 x H117 x D109 mm
  •                   W5.3 x H4.6 x D4.3 Inch
  • Enclosure Material : Stainless steel 316
  • Shipping Weight : 4.5 kg
  • Color : Metal
  • Conduit Entry Size : 2 x 1/2 inch NPT, M20X1.5

[  Electrical  ]

  • Operating Voltage : Typical DC24V (17 to 32)
  • Power Consumption : 3.6W minimum /4.8W maximum at 30 VDC
  • Wiring : 14AWG (2.08mm2) to
  •            24AWG (0.205mm2) shielded cable recommended.
  • Electromagnetic Compatibility : EMC Protected
Certificates and Documents