loader image
Get Brochure
Flame DetectorUVIR Flame Detector

UVIR Flame Detector | RFD-2000X-H

Flame Detector RFD-2000X-H is a UV / IR type hydrogen Flame Detector with international certifications.

  • Identify fire when both UV and IR sensors simultaneously detect the presence of a a hydrogen and hydrocarbon based flame.
  • Permits operation at Hazardous areas.
  • User selectable output options among Relays, 4-20 ㎃ stepped output, and RS-485.
Highlights
  • UV / IR Dual sensors
  • Detects Hydrogen and Hydrocarbon based flames
  • Enhanced False Alarm Immunity against sunlight and artificial false alarm sources
  • Approval for Explosion Proof and Dust Ignition proof
  • High reliability in operation with Automatic and Manual Self Diagnosis
  • Flame Detector RFD-2000X-H is suitable for hazardous areas such as Oil, Gas stations and Petrochemical plants
  • Field selectable sensitivity and delay time
specification
[  Specification  ]

  • Type : Ultraviolet and Infrared, Hydrogen flame detector
  • Field of View : Horizontal 90°, Vertical 90°
  • Temperature Range Operating : -40℃ to +75℃
  • Humidity Range : 0 to 95 % relative humidity
  • •performance : FM3260
  • Explosion proof :
  •   – Ex d IIB+H2 T6 IP67 (KCs)
  •   – Class I Division 1 Groups B,C and D (FMUS)
  •   – Class II/III Division 1 Groups E,F and G (FMUS)
  •   – T6: -40°F(-40°C) to +176°F (+75°C) (FMUS)
  •   – IP67/NEMA 4X (FMUS)
  •   – II 2 G Ex db IIB+H2 T6 (ATEX)
  • water tight : IP67 (KCs)
  • Output
  •   – Relay
  •    · Fire Alarm, Fault Alarm, Warning Alarm
  •    · From A or B Selectable, 28 VDC, 2 A
  •   – 4-20 mA
  •   – RS-485
[  Structure  ]

  • Dimensions : W134 x H117 x D120 (mm)
  •                 W5.3 x H4.6 x D4.7 (inch)
  • Enclosure Material : Stainless steel 316
  • Shipping Weight : 3.4 kg
  • Color : Metal
  • Conduit Entry Size : 2 x 1/2 inch NPT, M20 x 1.5

[  Electrical  ]

  • Operating Voltage : Typical DC24 V (17 to 32)
  • Power Consumption :  2.0 W minimum / 3.6 maximum at 32 VDC
  • Wiring : 14AWG(2.08mm2) to
  •            24AWG(0.205mm2) shield cable recommended.
  • Electromagnetic Compatibility : EMC Protected
Certificates and Documents