loader image
Get Brochure
Flame DetectorUVIR Flame Detector

UVIR Flame Detector | RFD-2FTN-I

Flame Detector RFD-2FTN-I is a UV / IR type Flame Detector identify fire when both UV and IR sensors simultaneously detect the presence of a flame.

  • Maximum 30 meters of detection range with a 100 degree cone of vision.
  • Permits operation at Hazardous areas.
  • User selectable output options among Relays, 4-20 ㎃ stepped output, and RS-485.
Highlights
  • UV / IR Dual-sensors
  • Wide field of view
  • Enhanced False Alarm Immunity against sunlight and artificial false alarm sources
  • Explosion-Proof and Dust Ignition proof
  • Flame Detector RFD-2FTN-I suitable for hazardous areas such as Oil, Gas stations and Petrochemical plants
  • Field selectable sensitivity and delay time
Specification
[  Specification  ]

  • Type : Ultraviolet and Infrared, Outdoor, Explosion-proof
  • Nominal sensing range : 30 m
  • Sensing angle : 100°, Cone type
  • Operating temp. : -40 ~ +75°C
  • Keeping temp. : -50 ~ +90°C
  • Humidity : 0~95%
  • performance :
  • – FM3260
  • – EN 50130-4 (CE)
  • Explosion proof :
  • – II 2 G Ex d IIC T5/T6 Gb(ATEX)
  • water tight : IP66/IP67
  • Output signal
  • – Relay
  • Fire : 1 A ( 250 VAC, 30 VDC ), A-B connect point
  • Error : 1 A ( 250 VAC, 30 VDC ), A-B connect point
  • – 4~20 mA
  • – RS485
  • Function
  • – Remote self diagnostic ON/OFF control ( BIT )
 [  Structure  ]

  • Material : Aluminum 6061
  • Surface : Anodizing Process
  • Color : White silver
  • Weight : About 0.53 kg
  • External : 64 × 64 × 75 mm, Hexahedral, Connector 1/2 NPT

[  Electrical  ]

  • Power Cunsumption : 2.0 W minimum / 3.6 W maximum
  • Voltage : DC 24 V, ( 17~32 V, pulsating current enable)
  • Current
  • – Idel(Sensing) : 55 mA
  • – Fire (Activating, Emergency) (Sensing) : 90 mA
  • – Self test : 170 mA
Certificates and Documents